1

Hello all,

I purchased a AP9631 on eBay and installed it in my SMT2200RM2U. It lit up, it pulled an IP address...but I can't connect to it. I reset it and it reconnected but no change.

I can ping it and the device IP config tool finds it. But when I try to bring it up, it doesn't connect. I've tried http/https. I tried with IE on Windows10, no dice.

I Googled with Bing and have tried some of the utilities on the APC site with no luck. I didn't find much around connecting to it. Am I missing something?

you are viewing a single comment's thread
view the rest of the comments
[-] jabuxm3@alien.top 1 points 11 months ago

My recommendation would be to get a serial cable for the apc management card and login to it to do a factory reset procedure. At that point you can run through the whole provisioning process and confirm that it’s all set up correctly and working as expected. I’ve had to do this with several 9631 devices over the years on smt750s and it works great thereafter. Also keep in mind that that firmware on the 9631 is separate from the firmware on the ups itself. Both may need to be updated independently from each other and shutdown entirely to be performed. Best to do it on the bench before placing them into service.

[-] warden_of_moments@alien.top 1 points 11 months ago

I’ll look at that doing that today.

this post was submitted on 25 Nov 2023
1 points (100.0% liked)

Homelab

371 readers
2 users here now

Rules

founded 1 year ago
MODERATORS